Unit display and interface cont, Mui menu navigation – WaterFurnace Series NXW User Manual

Page 26

Advertising
background image

26

ENVISION

2

NKW 50Hz REVERSIBLE CHILLER INSTALLATION MANUAL

Unit Display and Interface Cont.

MUI Menu Navigation

Welcome

Info Temp

Stat

Outputs

Settings

Maint

Alarm

ALM_History

Dual Stage Setpt
Reversible Chiller
PRODCWWE-10
MM/DD/YY

Info

Outputs

Comp 1 Status

ON

Comp 2 Status

OFF

RV Status

Heat

Acc 1 Status

OFF

Stg 1 Status

Normal

Stg 2 Status

Normal

EXPB01

OFF

EXPB02

OFF

EXPB07

OFF

Cp1 0

CP2 0

Outputs

Status

Unit Status

Auto

Y1 Status

OFF

Y2 Status

OFF

O Status

OFF

Emerg Shutdown OFF
Current Sens 1

OFF

Current Sens 2

OFF

Load Flow

OFF

Src Flow

OFF

Low Pres 1

ON

Hi Pres 1

NML

Low Pres 2

ON

Hi Pres 2

NML

Comp1 Low Limit NML
Comp2 Low Limit NML

Stat

Temperatures

Enter Load

25.1 ºC

Leave Load

10.5 ºC

Enter Source

21.1

1
1
1
1

1

°C

Leave Source

18.9 °C

Source Frz 1

25.4 °C

Source Frz 2

°C

Load Frz 1

°C

Load Frz 2

°C

Src Frz Setpt

°C

LD Frz Setpt

°C

Temp

Settings

Unit of Measure

C

CoolSetpt

XX.X

HeatSetpt

XXX.X

D NegThrshld

X.X

Int Rate

XXXXS

Mode

Aquastat

Stage Delay

XXX S

Sensor Select LWT
Gain

X.X

D PosThrshld

X.X

PIDY1 Ref

XXX

PID Y1 Diff

XX.X

PID Y2RefShift XX.X
PID Y2 Diff

XX.X

Settings

FP1

Log Off

FP2

Log Off

Int 1

XX.X

Temp Err

XX.X

RndmStrtDly

Run

Derivative

XX.X

Integ’r

Ena

PID Y1

Off

PID Y2

Off

D_Neg

Off

D_Pos

Off

O 2 Off O 4

Enum_0

Pos Err

Off

PID Out

XXX.X

Maintenance

Y1 Input

Off

Y2 Input

Off

B Input

Off

Emerg SD

Normal

Acc 1 Sel

On Comp

Lead/Lag Select On

Low Frz Setpt XX.X°C
Hi Frz Setpt

XX.X°C

Acc I Dly

XXXX S

LagCompDly

XXX S

Alarm

#Events

PreFrz1

0

Lo Press 1

0

Src Freeze 1

0

Ld Freeze 1

0

Bad Ld Sensor

0

Lo Press 2

0

Src Freeze 2

0

PreFrz 2

0

Hi Press 1

0

Bad Src Sensor

0

Ld Freeze 2

0

Hi Press 2

0

StrtFail 1

0

StrtFail 2

0

Alarm History

Maintenance

ALARM SUMMARY

^/High Pressure

Alarm

When in the stat page, press the

right arrow once to go this screen

NOTE: This FX10 application implements an alarm history which is reset
only by cycling power. This history shows on the Alm-History page. Any
alarm showing 2+ events has occurred more than 2 times.

Alarm lock-outs are reset by cycling power, by pres s ing the “E S C ” and
Return

keys simultaneously for a minimum of 15 seconds, or by

commanding the nviAlarmReset over the BAS network.

Test mode is enabled by holding the ‘E s c’ and Down Arrow s imultaneous ly
for a minimum of 15 seconds and releasing. Test mode times out after 30
minutes, and may als o be ended by pres s ing ‘E S C ’ and Up Arrow
simultaneously and releasing. Test Mode bypasses the On Delay (90 sec)
and Random Start timers for quicker troubleshooting. It also allows cycling
the reversing valve without compressor shutdown.

Advertising