Pressure drop – WaterFurnace Series NXW User Manual

Page 30

Advertising
background image

30

ENVISION

2

NKW 50Hz REVERSIBLE CHILLER INSTALLATION MANUAL

Pressure Drop

Note: Pressure drop is the same for load and source heat exchangers at 30°F fluid temperature.

Model

L/s

Pressure Drop (kPa)

0°C

10°C

20°C

30°C

45°C

030

1.3

5.5

4.8

4.1

4.1

3.4

1.9

14.5

13.1

12.4

11.7

10.3

2.5

22.8

21.4

20.0

19.3

17.2

045

1.9

6.3

5.5

5.1

4.9

4.0

2.8

15.9

14.8

13.8

13.4

12.4

3.8

25.7

24.1

23.0

22.1

20.1

060

2.5

8.9

8.2

7.9

7.5

6.6

3.8

21.7

20.7

20.0

19.3

17.9

5.1

34.3

32.6

31.4

30.6

28.6

090

3.8

8.6

7.9

7.4

6.9

6.1

5.7

21.0

20.0

19.3

18.6

16.5

7.6

32.9

31.4

30.3

29.6

27.2

150

6.3

19.0

17.6

16.5

15.4

14.0

9.5

32.4

31.0

30.3

27.8

26.8

12.6

43.9

42.5

41.8

39.3

38.3