Operating parameters, Pressure drop – WaterFurnace Series NXW User Manual

Page 29

Advertising
background image

29

ENVISION

2

NKW 50Hz REVERSIBLE CHILLER INSTALLATION MANUAL

Operating Parameters

Heating Mode

Entering

Load Temp (

o

C)

Entering

Source Temp (

o

C)

Suction

Pressure (kPa)

Discharge

Pressure (kPa)

Superheat

(

o

C)

Subcooling

(

o

C)

15

0

517-690

1379-1482

6-7

6-7

10

690-862

1379-1482

7-8

4-7

20

862-1034

1482-1586

8-10

4-7

30

1034-1138

1586-1758

14-17

4-7

25

0

517-690

1965-2069

6-7

6-7

10

690-862

2069-2172

7-8

4-7

20

862-1034

2172-2275

8-10

4-7

30

1034-1138

2275-2379

14-17

4-7

40

0

586-758

2517-2620

6-7

4-6

10

758-931

2655-2758

7-8

4-6

20

931-1138

2758-2861

8-10

2-4

50

10

758-931

3344-3448

7-8

4-6

20

931-1138

3448-3551

8-10

2-4

Note: Operating data based on normal conditions with 4.3 L/min per kW for the load and source. 10/7/14

Cooling Mode

Entering

Load Temp (

o

C)

Entering

Source Temp (

o

C)

Suction

Pressure (kPa)

Discharge

Pressure (kPa)

Superheat

(

o

C)

Subcooling

(

o

C)

10

0

552-621

965-1207

8-11

2-3

10

621-690

1379-1620

6-8

3-5

20

690-758

1724-1965

6-8

5-7

30

690-827

2275-2517

4-7

7-8

45

758-896

2965-3206

4-7

8-11

20

0

552-621

1034-1276

8-11

2-3

10

621-690

1448-1689

6-8

3-5

20

690-758

1793-2034

6-8

5-7

30

758-827

2344-2586

4-7

7-8

45

758-965

3034-3344

4-7

8-11

30

0

552-621

1034-1276

8-11

2-3

10

621-690

1448-1689

6-8

3-5

20

690-758

1793-2034

6-8

5-7

30

758-827

2344-2586

4-7

7-8

45

0

621-690

1103-1345

22-25

2-3

10

758-896

1517-1758

17-22

3-5

Note: Operating data based on normal conditions with 4.3 L/min per kW for the load and source. 10/7/14