Table 1 – CIRCUTOR DHB Series User Manual

Page 18

Advertising
background image

18

Table 1

Para-

meter

symbol

Description

Range of changes

tYP

Choice of the displayed quantity

U – RMS voltage
I – RMS current
P – active power
q – reactive power
S – apparent power
PF – factor of active power
tG – ratio of reactive power to the

active power
FI – phase shift
FrEq - frequency
EPPoS – active energy input
EPneg – active energy output
EqPoS – reactive energy input
Eqneg – reactive energy output
PAv – mean active power
UAv – 10 minutes’ mean voltage
FAv – 10 seconds’ mean frequency
HoUr – current time

SYn

Type of input synchronization

U – synchronization with voltage

(measurement of all values)
I – synchronization with current

(only measurement of current and
frequency)

rAnU

Choice of voltage range

100U – range 100 V
400U – range 400 V

rAnI

Choice of current range

1A – range 1 A
5A – range 5 A

trU

Choice of voltage ratio

1...4000.0

trI

Choice of current ratio

1...10000

PAv S

Synchronization of averaged active
power

15 – 15 minutes walking window
c_15 – measurement every 15 minutes

synchronized with the clock
c_30 – measurement every 30 minutes

synchronized with the clock
c_15 – measurement every 60 minutes

synchronized with the clock