CIRCUTOR DHB Series User Manual

Page 50

Advertising
background image

50

- input signal

0...0.005...1.2I

n

; 0.05...1.2U

n

for

current, voltage

0...0.1...1.2I

n

; 0...0.1...1.2U

n

; for

coefficients Pf

i

, t

j

i

,

j

frequency

45...66...100 Hz;

sinusoidal (THD

 8%)

- power factor

-1...0...1

- ambient temperature -25...23...+55°C
- storage temperature

-30...+70°C

- relative air humidity

25...95% (

inadmissible condensation

)

- admissible peak factor of:

- current

2

- voltage

2

- external magnetic field

0...400 A/m

- short duration overload (5 s):

- voltage inputs

2Un (max.1000 V)

- current inputs

10 In

- work position

any

- minimal distance between meters 1.5 cm
- power consumption:

- supply circuit < 6 VA

- in voltage/current circuit < 0.05 VA.

- input power

6 VA

Additional Errors in % of the basic error:
- from frequency of input signals

< 50%

- from ambient temperature changes

< 50%/10°C

Standards Fulfilled by the Meter:
Electromagnetic Compatybility:

- noise immunity acc.to EN 61000-6-2

- noise emissions acc. to EN 61000-6-4
Safety Requirements: acc. to EN 61010-1 standard

l

isolation between circuits: basic,

l

installation category III,

l

pollution level 2,

l

maximal earth-to-phase voltage 600 V

l

altitude above sea level < 2000 m,

Preheating Time

15 minutes