Technical data, Measuring ranges table 8 relay outputs, Voltage programmable 0 v load resistance ³ 500 w – CIRCUTOR DHB Series User Manual

Page 48: Galvanically isolated, Resolution 0.01% of the range

Advertising
background image

48

Measured value

Indication range

Measuring range

Basic error

Current 1 A

0.000...12 kA

0.005...1.200 A~

±0.2%

5 A

0.000... 60 kA

0.025...6.000 A~

Voltage L-N

100 V

0.0...0.48 MV

0.5...120 V

±0.2%

400 V 0.0 ...1.92 MV 2.0...480 V

Frequency

45.00...100.00 Hz

45.0...66.0...100 Hz

±0.2%

Active power

-19999... 99999 MW

-2.88 kW...1.40 W...2.88 kW

±0.5%

Reactive power

-19999 Mvar...0.00

...99999 Mvar

-2.88 kvar...1.40 var...2.88 kvar

±0.5%

Apparent power

0.00...99999 MVA

1.40 VA... 2.88 kVA

±0.5%

Coefficient PF

-1...0...1

-1...0...1

±0.5%

Tangens

j

i

-1.2...0...1.2 -1.2...0...1.2 ±1%

j

0...359

0...359 ±1%

Active energy

0...9 999 999.9 kWh

0...9 999 999.9 kWh

±0.5%

Reactive energy

0...9 999 999.9 kvarh

0...9 999 999.9 kvarh

±0.5%

Current time

0.00...23.59

0.00...23.59

1 second

/24 h

Ku – voltage transformer ratio: 0.1...4000.0
Ki – current transformer ratio: 1...10000

8. TECHNICAL DATA

Measuring Ranges

Table 8

Relay outputs

l

relays, voltageless NOC contacts

load-carrying capacity 250 V/0.5 A

l

relays, voltageless switched contacts

load-carrying capacity 250 V/0.5 A

(DHB-324)

Analog output (DHB-324)

l

current programmable 0/4...20 mA

load resistance

 500 W

l

voltage programmable 0...10 V

load resistance

³ 500 W

l

galvanically isolated

l

resolution 0.01% of the range