Voltage input range

4002

rAn U

w/r

0...1

Value

0

Range 100 V

1

Range 400 V

Current input range

4003

rAn I

w/r

0...1

Value

0

Range 1 A

1

Range 5 A

Voltage ratio *0.1

4004

tr u

w/r

1...40000

Current ratio

4005

tr I

w/r

1...10000

Synchronization of averaged active power

4006

PAv S

w/r

0...1

Value

0 Walking window

4007

Reserved

4008

Reserved

Minimal decimal point

4009

dP

w/r

0...10

Value

0 0.0000
1 00.000
2 000.00
3 0000.0
4 00000

5

k 000.00

6

k 0000.0

7

k 00000

8

M 000.00

9

M 0000.0

10

M 00000

Display colour when the displayed value is less than

in the register 7600

4010

CoLdo

w/r

0...2

Value

0 red
1 green
2 orange

1 Measurement every 15 minutes synchronized

with the internal clock

2 Measurement every 30 minutes synchronized

with the internal clock

3 Measurement every 60 minutes synchronized

with the internal clock