3�2�-INSTALLATION

The

Computer SMART III FASTregulatorisconnectedtounitsthatcontainca-

pacitors,whichremainchargedafterthevoltagesourceisdisconnected�

Wait at

least 5 minutes aftertheunitisdisconnectedbeforehandlingitsinternalcom-

ponentsinordertoavoidtheriskofelectricshock�

Any manipulation or use of the unit other than that specified by the manu-

facturer may compromise user safety�

Makesurethattheunitsarecorrectlyearthedbeforetheyareconnected�Afaultyearthconnec-

tioncouldleadtofaultyoperationandleadtoariskofelectricalshockfortheuserorperson

handlingtheunit�

Resonancecanoccurwhentheunitisconnectedwithnoload�Inthiscase,thevoltagehar-

monicscanbeamplified,causingdamagetothecompensationunitandotherunitsconnected

tothemains�

Thesafeuseofthe

COMPUTER SMART III FASTrequiresthepersonsinstallingorhandling

ittofollowthegeneralsafetymeasuresofLVelectricalinstallations,aswellasthewarnings

indicatedinthisinstructionmanual�

Theunitwillbeinstalledonapanel(138+1

x138+1mmpaneldrillhole,incompliancewithDIN

43700)�Allconnectionsareinsidetheelectricpanel�

Terminals,openingroofsorremovingelementscanexposepartsthatarehaz-

ardoustothetouchwhiletheunitispowered�Donotusetheunituntilitisfully

installed�

Theunitmustbeconnectedtoapowercircuitthatisprotectedwithgl(IEC269)orMtypefuses

witharatingof0�5to2A�Itmustbefittedwithacircuitbreakerorequivalentdevicefordiscon-

nectingtheunitfromthepowersupplymains�

Thepowerandvoltagemeasurementcircuitsaswellastherelaycontactcircuitsmustbecon-

nectedwithcablesthathaveaminimumcross-sectionof1�5mm

2

Oneorthreeexternalcurrenttransformers(CT)needtobeinstalledinordertomeasurecur-

rent�Usually,thetransformationratiooftheseCTsisIn/5A,whereInisatleast1�5timesthe

totalmaximumloadcurrent�

Thesecondarycablesofthecurrenttransformers(CT)musthaveaminimumcross-section

of2�5mm

2

�FordistancesbetweentheCTsandtheunitofmorethan25m,thiscross-section

shouldbeincreasedby1mm

2

forevery10m�

Thecurrenttransformers(CT)mustbeinstalledatapointinthedistributionpanelwhichcarries

allthecurrentoftheloadstobecompensatedaswellasthecurrentofthecapacitorsthem-

selves(

Figure 1

)�

10

Computer SMART III FAST

Instruction Manual