1 four-quadrant regulator, 2 stages and steps, 3 fcp system (fast computerized program) – CIRCUTOR computer SMART III-Fast Series User Manual

Page 23: 4 regulation program

Advertising
background image

4�1�-DEFINITIONS

Thissectionprovidesanumberofdefinitionsthatmaybeusefulforunderstandingtheopera-

tionoftheunit�

4�1�1 Four-quadrant regulator�

Thismeansthattheregulatoriscapableofperformingthemeasurementandregulationfunc-

tionswhentheactivepoweristransferredfromthemainstotheloads(commoncaseinacon-

sumerinstallation)orwhentheloadistransferredtothemains(inthecaseofinstallationswith

generatorsthatnotonlyallowtheconsumptionofenergy,butcanalsoexportandsellenergy)�

4�1�2 Stages and steps

Adistinctionmustbeestablishedbetweenstagesandsteps�Inthismanual,a

Stage is de-

scribedaseachgroupofcapacitorbanksintowhichthepowerfactorcompensationunitis

divided,whichmayhavedifferentpowerratings,usuallyinratiosof1:1,1:2,1:2:4,etc�

A

stepiseachoneofthetotalpowerfractions(powerofthefirststep)thatcanberegulatedby

usingstageswithdifferentweights�

4�1�3 FCP system (FAST Computerized Program)�

Thissystemcontrolstheconnectionsequenceofthevariousstages,tendingtominimisethe

numberofoperationsandtomatchtheusagetimesofthevariousstagesinordertoachieve

apre-determinedrequiredfinalpower�Theoperationsarecarriedoutsuchthat,inthecase

ofstageswithidenticalpower,thestagethathasbeendisconnectedthelongestisconnected

whenthereisdemandandthestagethathasbeenconnectedthelongestisdisconnected

whenthereisasurplus�

4�1�4 Regulation program�

Thepowerratingsofthevariousgroupsorstagesusuallyfollowcertainpatternscalled"pro-

grams”�

Theprogramindicatesthepowerratiosbetweenthevariousstages�Themostfrequentpro-

gramsare:

Program 1�1�1�1 �Allstageshavethesamepower�For example: a 100 kvar unit with 5 steps

would be made up of 5 identical 20 kvar stages, and would be described as a (5 x 20) kvar unit.

Program 1�2�2�2�Everystageafterthefirststagehastwiceasmuchpowerasthefirststage�

For example: a 180 kvar unit with 5 stages would be made up of a first 20 kvar stage and 4

identical 40 kvar stages, and would be described as a (20 + 4 x 40) kvar unit.

Program 1�2�4�4�Thesecondstagehastwiceasmuchpowerasthefirststageandthere-

mainingstagesafterthesecondstagehavefourtimesasmuchpowerasthefirststage�

For

example: a 300 kvar unit with 5 stages would be made up of a first 20 kvar stage, a second 40

kvar stage and 3 identical 80 kvar stages. It would be described as a (20 + 40 + 3 x 80) kvar

unit.