Example of a modbus query – CIRCUTOR computer SMART III-Fast Series User Manual

Page 68

Advertising
background image

OutputassociatedwithAlarmE01

1170

0(No),

1(Alarmrelay),

2(Digitaloutput1)

2(Digitaloutput2)

0

OutputassociatedwithAlarmE02

1171

0

OutputassociatedwithAlarmE03

1172

0

OutputassociatedwithAlarmE04

1173

0

OutputassociatedwithAlarmE05

1174

0

OutputassociatedwithAlarmE06

1175

0

OutputassociatedwithAlarmE07

1176

0

OutputassociatedwithAlarmE08

1177

0

OutputassociatedwithAlarmE09

1179

0

OutputassociatedwithAlarmE10

1179

0

OutputassociatedwithAlarmE11

117A

0

OutputassociatedwithAlarmE12

117B

0

OutputassociatedwithAlarmE13

117C

0

OutputassociatedwithAlarmE14

117D

0

OutputassociatedwithAlarmE15

117E

0

OutputassociatedwithAlarmE16

117F

0

OutputassociatedwithAlarmE17

1180

0

C�-Deleting parameters

Parameterscanbedeletedusing

Function 05:writingarelay�

Table 37:Modbus memory map: deleting parameters

Deleting parameters

Action

Address

Value to be sent

Deletingmaximumvalues

200

FF

Deletingminimumvalues

210

FF

Deletingmaximumandminimumvalues

220

FF

Deletingenergies

230

FF

Deletingthestagesearchandstageenablingvaluesoftheleakagecurrent

alarm

240

FF

Deletingtheno�ofoperationsofalltherelays

250

FF

ResettingalarmsE14andE15

260

FF

Restoringthedefaultconfigurationvalues

300

FF

4�9�4� EXAMPLE OF A MODBUS QUERY

Query:InstantaneousvalueoftheL1phasevoltage

Address

Func-

tion

Initial log

No� of logs

CRC

0A

04

0000

0002

70B0

Address: 0A,Peripheralnumber:10indecimal�

Function: 04,Readfunction�

Initial Log: 0000,logfromwhichtostartreading�

No� of logs: 0002,numberoflogstoberead�

CRC: 70B0,CRCcharacter�

68

Computer SMART III FAST

Instruction Manual

Advertising
This manual is related to the following products: