Voltage thd alarm – CIRCUTOR computer SMART III-Fast Series User Manual

Page 96

Advertising
background image

5�22�-VOLTAGETHDALARM

InthispointthethresholdsabovewhichtheVoltage
THDalarm(

E08

)isactivatedcanbeconfigured�

Thealarmmustbeenabled(

5�19�- ENABLING

ALARMS”

The programmed values are useful for the 3

phaseswhichtheunitmeasures�

Pressthe

keytoentereditingmode�Itis

identifiedbythe

symbolandtheblinkingof

thedigitstobemodified�

Theparameterstobeconfiguredare:

The

Lo

value : whentheunitexceedsthisvaluefor30minutes,alarm

E08

is

triggered,andifalarm

E11

isenabled,the

SMART III FASTunitentersNo Connection

statusandactivates

alarm

E11

The

HI

value: iftheunitexceedsthisvaluefor30seconds,alarm

E08

istriggered,

andifalarm

E12

isenabled,the

SMART III FASTunitentersDisconnection statusand

activates

alarm

E12


Iftheunitfallsbackunderthe

Lo

valuefor10minutes,itdeactivatesthealarmsandreturns

tothenormaloperatingstatus�

Inthe

No Connectionstatus,theunitdoesnotconnectthestages,butalsodoesnot

disconnectthemiftheoperationrequiresit�

Inthe

Disconnectionstatus,itdisconnectsthestagesanddoesnotallowthemtoconnect�

The

keyincreasesthedigitvalue�

The

keydecreasesthedigitvalue�

The

keyskipstothepreviousdigit�

The

keyskipstothenextdigit�

Press

tovalidatethedata;the

symboldisappearsfromthedisplay�

Lo

Valueand

HI

Value:

Maximum value: 99%

Minimum value: 1%

96

Computer SMART III FAST

Instruction Manual