3�5�7�- Leakage current connection, IΔ

Tomeasuretheleakagecurrent,anearthleakagetransformermustbeused,suchas

WGS

Theleakagecurrenttransformermustbeconnectedsuchastomeasurethecurrentofthe

capacitorbank�Thiswilldetectanyleakageinthecapacitorsofthecapacitorbank�

~

TC

LOAD

CAPACITORS

S1

S2

P1

P2

I

S1

S1

S2

S2

I

L1,

I

L2,

I

L3

Figure 9: Connection of the leakage current transformer (I

Δ

)�

NB: The earth leakage transformer must have a ratio of 500 turns. The maximum leakage cur-

rent that the unit can measure correctly is 1.5A AC, even though the maximum input is 5A AC

via the earth leakage transformer.

Donotoperatetheleakagecurrenttransformerwiththe

Computer SMART III

FASTpoweredon�

20

Computer SMART III FAST

Instruction Manual