CIRCUTOR OPTIM HYB Series User Manual

Page 23

Advertising
background image

Figure 14: Quadrupole circuit breaker for the auxiliary power circuit.

5.- Connect the power supply of the OPTIM HYB capacitor bank, closing the general quadru-

pole switch inside the capacitor bank using its lever (ON position) and check that the

CPU LED

and the

RS485 COM 2 RX and TX LEDs light up immediately and flash at an approximate rate

of once per second.

This indicates the correct operation of the

Computer HYB processor and correct communica-

tions between the

Computer HYB and the CVM-MINI-RS485, respectively.

6.- Check that the CVM-MINI-RS485 (in the OPTIM HYB models that come equipped with it)

installed in the door of the capacitor bank lights up, and then program the primary value of the

current transformers that provide the measurement signal to the analyzer. Follow the steps

below for this programming:

A.- Access the MEASUREMENT Setup by pressing the SETUP key until the unit enters

into programming mode.

The screen shown in

Figure 15

will appear on the display, which allows you to program

the voltage primary.

Note : This programming is not necessary for 3 x 400 V / 1 x 230 V networks.

s e t

Pr i U

0 0 0 0 0 1

Figure 15: Programming of the voltage primary, CVM-MINI-RS485.

B.- Press the

key until the screen shown in

Figure 16

appears on the display, which

allows you to program the current transformer primary.

s e t

p r i a

0 0 0 0 5

Figure 16: Programming of the current primary, CVM-MINI-RS485.

To enter or modify the current primary, press the

max

key repeatedly to increase the

23

Instruction Manual

OPTIM HYB Series