Fig. 5 example 1, 2 and 3 windings – Crompton Controls M10 User Manual

Page 14

Advertising
background image

12

Selecting the current transformer

Emotron AB 01-2550-01r3

Fig. 4

Example CTM 025 with 2 windings for a 12 A motor

Fig. 5

Example 1, 2 and 3 windings.

NOTE: Normally the appropriate Current Transformer (CTM XXX) will have
been ordered and shipped with the Emotron M10. Check that this is the
case; contact the supplier if in doubt.

CAUTION: Terminals 1 and 2 (S1, S2) carry live voltage.

NOTE: The current transformer connection and orientation are not polarity
sensitive, but must be connected to the same phase that is being referenced
for terminal 9 of the Emotron M10.

L1

L2

L3

1

2

S1 S2

M

3

M10

2 windings

CTM025

P2

1

2

P2

5:1

5:2

5:3