4 getting started, 1 please take note of the safety section, 2 connection and set-up before first start – Crompton Controls M10 User Manual

Page 8: Getting started, Please take note of the safety section, Connection and set-up before first start, 4getting started

Advertising
background image

6

Getting Started

Emotron AB 01-2550-01r3

4

Getting Started

4.1

Please take note of the safety section

1. Pay special attention to the safety section in this manual and the parts

marked CAUTION.

2. Check that the motor/supply voltage corresponds to the values on the

Emotron M10 product label at the side of the monitor.

3. Make a note of the motor's rated power and rated current from its name-

plate. Confirm that the current transformer supplied is of the correct size
according to table 1, page 11 in this manual.

4.2

Connection and set-up before first start

1. Connect the Emotron M10 according to Chapter 5 and Fig. 1.

2. Make sure all safety measures have been implemented and switch on the

supply voltage - Power LED turns green.

3. Minimum parameters to be set are "Rated Power" and desired relay function

"Max or Min", see Chapter 8, Table 2, 3 and Fig. 6.

4. Press PAR once - "LED" AUTO SET turns green.

5. Keep pressing PAR until the desired parameter is selected e.g. RATED

POWER, see Chapter 8, Table 2 and 3.

6. Press VAL - Factory set value or earlier set value flashes e.g. "64".

7. Keep pressing VAL until desired value is displayed (0 - 64).

8. Confirm chosen value by pressing PAR.

9. Press PAR again and repeat steps 4 to 8 for all parameters except for AUTO

SET. See Chapter 8, Table 2, 3 and Fig. 6 for possible value settings for
each of the eight parameters.

10. Start and run the motor/system at normal load conditions, also wait until

the START DELAY has expired.

HINT!

Short-circuit the output relay during the set-up, this prevents the equipment
stopping unintentionally, see Hint! in Chapter 5.

11. Press PAR once - "LED" AUTO SET turns green.

Advertising