Programming

Emotron AB 01-2550-01r3

More hints

If the alarm level is difficult to set - simply perform an Auto Set when the
motor is stopped. Then start the machine, run at normal load and perform
an Auto Set again.

If a wrong value is unintentionally set - simply set a new value. If the value is
not confirmed by pressing PAR, the new value is not accepted (time out
after 30 seconds).

Table 2

Parameters and values.

Parameter

Value

Factory

setting

Note

RATED POWER

0 1 2 4 8 16 32 64

64

See table 3

RELAY INVERTED 0 (no) 1 (yes)

0

0 = Relay activated at alarm

ALARM
CURRENT = 0

0 (no) 1 (yes)

0

Alarm at no motor current

MAX OR MIN

0 (MIN) 1 (MAX)

1

0 = under load
1 = overload alarm

RESPONSE
DELAY

0 1 2 4 8 16 32 64

2

Response delay in seconds
(0=50 ms)

START DELAY

0 1 2 4 8 16 32 64

2

Start delay in seconds

MARGIN (% of
rated power)

0 1 2 4 8 16 32 64

8

Load change for alarm
sensitivity, Fig. 7

AUTO SET

Auto Set load level is
automatically set if
VAL key is pressed for
3 seconds.

VAL key must be pressed
when LED parameter AUTO
SET is light. LED bar is
switched off when Auto Set
level is set.