1 terminals, Terminals – Crompton Controls M10 User Manual

Page 23

Advertising
background image

Emotron AB 01-2550-01r3

Parameter list

21

9.1

Terminals

1)

Note! Terminals 1 and 2 (S1, S2) carry line voltage.

2)

N must be connected to terminal 11 and 13 (single phase).

Table 5

Terminals and labels

Terminal

Label

Function

1

S1

Current transformer input for CTM 010, CTM 025 or
CTM 050, blue wire

1

2

S2

Current transformer input, brown wire

1)

3

(not used)

4

(not used)

5

RES

Reset input. Latched or unlatched alarm is selected via
this input. Connect to + at DC.

6

C

Alarm relay common and also reset common. Connect to
“-” at DC.

7

NC

Alarm relay normally closed

8

NO

Alarm relay normally open

9

L1

Motor voltage phase L1

10

(not used)

11

L2

Motor voltage phase L2 (N for single phase motors)

2)

12

(not used)

13

L3

Motor voltage phase L3 (N for single phase motors)

2)