2 auto set, Auto set, M10 par – Crompton Controls M10 User Manual

Page 16: Reset input, Current input, Relay output, Motor terminals, Power/alarm, Reset, Terminal 6, 7 and 8 output relay

Advertising
background image

14

Operation

Emotron AB 01-2550-01r3

7.2

Auto Set

The alarm load level is automatically set by the Auto set function, see Chapter 8

The value for a parameter, e.g. seconds, kW, HP or margin, can only be set as
0, 1, 2, 4, 8, 16, 32 or 64. Select closest value.

The Emotron M10 with article number 01-3160-00 "Fast Response" (M10 FR)
is identical with the standard Emotron M10 except for where the start-up delay
and the response delay are shorter than below:

Article number 01-2487-10 standard Emotron M10:
RESPONSE DELAY: 0.05 - 64 s
START-UP DELAY: 1 - 64 s

Article number 01-3160-00 "Fast Response" (M10 FR):
RESPONSE DELAY: 0.05 - 6.4 s
START-UP DELAY: 0.1 - 6.4 s

PAR

VAL

RESET 3s.

Rated Power

Relay Inverted

Alarm Current=0

Max Or Min

Response Delay

Start Delay

Margin

Auto Set

64

32

16

8

4

2

1

0

Power /
Alarm

11

L2

13

L3

9

L1

8

NO

7

NC

6

C

2

S2

1

S1

5

RES

M10

PAR

Parameter change
(LED light constant
green) - pressing PAR
key when parameter is
displayed proceeds to
next parameter.

VAL

Value setting - Pressing
VAL key when green LED is
flashing increases value. A
changed value is con-
firmed by pressing PAR.

Reset input

Terminal 5 and 6 are used
for external reset and selec-
tion of latched/unlatched
alarm.

Current input

Terminal 1 and 2. Cur-
rent Transformer; CTM
010, 025 or 050 (Max.
50 A motor).

Relay output

Terminal 6, 7 and 8 output
relay.

Motor terminals

Terminal 9 (L1), 11 (L2)
and 13 (L3) for supply and
motor voltage input.

Power/Alarm

The Power/Alarm LED
turns green at "power
on" and at normal load.
Red at alarm.

Reset

Reset a latched alarm
by pressing both PAR
and VAL at the same
time for 3 seconds.