Stove installation – Avalon Firestyles Olympic User Manual

Page 15

Advertising
background image

Stove

Installation

(for qualified installers only)

15

© Travis Industries

93508061

4150520

Exterior Factory
Built Chimney

NOTE:

Exterior chimneys are
subject to greater
moisture and creosote
accumulation due to the
lower temperatures. An
insulated chase will
reduce these
accumulations (the
proper clearances to the
chimney must be
maintained).

Figure 12

Hearth Stove
Positive
Connection

NOTE:

Most factory-built
chimney manufacturers
make stainless steel
chimney liners, either
flexible or rigid. This
provides a wide variety
of installation options.
Make sure to follow the
manufacturer's
instructions for
installation and support.

Figure 13

Chimney Cap
(See the section "Chimney
Termination Requirements"
for more details)

Chimney Sections

Minimum Air Space to
Combustibles (See
Chimney Manufacturer's
Instructions - usually 2")

Chimney Connector
Sections

Follow the chimney
manufacturer's
instructions and
clearances for roof
penetrations. A storm
collar and flashing are
required (some
require a radiation
shield).

}

Stove Clearances
(See the section "Stove
Placement Requirements"
for more details)

}

Follow the chimney
manufacturer's
instructions and
clearances for wall
penetrations. A
wall radiation shield
(thimble) is
required.

Optional
insulated
chase

Wall Bands
and
Supports

Insulated Tee
(with cleanout )

Minimum 15'
Maximum 33'

Min. 18"
clearance to
ceiling

Floor Protection
(See "Floor
Protection
Requirements"
for details)

Remove damper
or wire it open

Airtight Insulated
Clean-Out

Min. 18"

Combustible
Mantle

NOTE: The entire fireplace and
chimney must be clean, undamaged,
and meet all local building codes
(UBC, etc.). Damage must be
repaired prior to installation. The
chimney must be 15' to 33' tall.

Floor Protection
(See the section
"Floor Protection
Requirements"
for more details)

See the section
"Stove Placement
Requirements" for
minimum clearances
required.

The liner must be
stainless steel connector
or flexible vent. Follow
the liner manufacturer's
instructions for installation
and support.

Cap and flashing
prevents water from
entering