Vertical terminations with two 90 elbows, Nstallation – Avalon Firestyles DVS Fireplace-1997 to 2000 User Manual

Page 20

Advertising
background image

P

AGE

20

I

NSTALLATION

(C

ONT

.)

- For Qualified Installers Only!

Approved Venting Configurations for Vertical Terminations with Two 90¡ Elbows

¥ The termination must fall within the shaded area shown in the chart. Use the indicated restrictor position.

NOTE:
Horizontal sections require a 1/4" rise
every 12" of travel.

Restrictor

Position #3

NOTE:
Restrictor positions are
based upon lab tests.
The ideal restrictor
position may vary
slightly, especially when
the termination is near a
demarkation line.

Restrictor

Position # 2

NOTE:
A min. 8' of vertical vent
must be used.

0 feet

5 feet

10 feet

0 feet

0 feet

0 feet

16' (max)

5 feet

10' (min)

15 feet

20 feet

25 feet

30 feet

35 feet

5 feet

10' (min)

15 feet

20 feet

25 feet

30 feet

35 feet

5 feet

10 feet

16'( max)

37' (max)

37' (max)