ADDENDUM #1 Class A Chimney
Conversion Kit

Simpson Duravent provides a conversion kit for those wishing to use
an existing wood stove chimney to vent this direct vent stove. The
illustration below gives an overview of this type of installation. See
the instructions included with the kit for details.

!

Do not exceed the maximum vertical rise (see the section "Approved
Vent Configurations" starting on page 9) allowable. Remember to set
the restrictor position to the correct position (based upon the vertical
rise height - see the chart on page 10).

!

The conversion kit does not work on interior masonry chimneys.

Chimney Conversion Kit A (# 931)

Metalbestos 6" I.D.
Security Chimneys 6" I.D.
Jackes-Evans 6" I.D.
Hart & Cooley 6" I.D.
Pro-Jet 6" I.D.
Chimney Conversion Kit B (# 932)

Simpson Dura-Vent 6" I.D.
Air-Jet 6" I.D.
Metal-Fab 6" and 7" I.D.
Amer. Metals 6" & 7" I.D.
Metalbestos 7" and 8" I.D.
Jackes-Evans 7" and 8" I.D.
Hart & Cooley 7" and 8" I.D.
Pro-Jet 7" and 8" I.D.
Security Chimneys 8" I.D.
Chimney Conversion Kit C (# 933)

Simpson Dura-Vent 7" and 8" I.D.
American Metals 8" I.D.
Air-Jet 8" I.D.
Metal-Fab 8" I.D.
American Metals 8" I.D.
Each Kit Contains:

Retro Connector
Retro Vertical Top
Additional Required Equipment:

4" Flex (#711 or U.L. 1777)
Termination (#991)
Co-Axial Sections

Type A Chimney

Simpson Duravent Direct
Vent Pipe Sections
(use adjustable section)

Screw the Retro
Vertical Top to the
Flex Pipe

Retro Vertical Top
(screw to chimney)

Screw the Retro
Connector to the
Flex Pipe

Retro Connector
(screw to chimney)

4" (100 mm)
Aluminum Flex
Pipe

Cut the Flex Pipe to
the chimney height
plus 3" (75 mm)

ADDENDUM #2 Interior
Masonry Chimney
Conversions

Follow the requirements and use the
equipment listed in the illustration to
the right to install this appliance into
an interior masonry chimney.

Maximum vertical rise is 40'

Minimum vertical rise is 10'

See the chart on page 12 for
determining the correct restrictor
position.
NOTE: these restrictor positions are
based upon lab tests. The ideal
restrictor position may vary slightly.

The entire chimney system

must be air-tight. Make sure to

seal the flashing, clean-out,

and thimble connection, and to

inspect the chimney.

#711 Flex Liner (4” dia.)

(or other UL 1777 Gas

Liner)

Co-Axial Straight

Lengths

#991 High Wind

Termination

#990 90° Elbow

Flashing (included in

#934 Masonry

Conversion Kit

Make sure the coaxial pipe

maintains a 1” clearance to any

combustible. The vent must be

sealed air-tight.

High-Temp.

Silicone

Connector with Cover

(included in #934 Masonry

Conversion Kit)

Interior Masonry Chimney

Standard Masonry Fireplace

Connector (included in #934

Masonry Conversion Kit)

secured and sealed to

block-off plate.

Flashing (included in

#934 Masonry

Conversion Kit)

#991 High Wind

Termination

#711 Flex Liner (4” dia.)

(or other UL 1777 Gas Liner)

The entire chimney system

must be air-tight. Seal the

connector cover and inspect

the chimney.

Make sure the coaxial pipe

maintains a 1” clearance to any

combustible. The vent must be

sealed air-tight.