Specifications – Basler Electric BE1-50/51B-240 User Manual

Page 10

Advertising
background image

2

9252000790 Rev B

Built-in accuracy eliminates internal adjustments

Minimum transient overreach

Field selectable characteristic curve selection similar to GE IAC or Westinghouse CO type curves

Field selectable instantaneous or integrating reset

Field selectable 50 or 60 Hz operation

Field selectable 0.0 or 0.1 second, fixed, instantaneous delay

Internal switches provide for selecting system-operating frequencies of 50 or 60 Hz, instantaneous
element delays of 0.0 or 0.1 second, characteristic curve group selection for either GE IAC or
Westinghouse CO type curves, and instantaneous or integrating reset characteristics. Switch locations
and descriptions are provided in the Controls and Indicators chapter.

Advantages

The BE1-50/51B-240 overcurrent relay has many advantages over other overcurrent relays. The primary
advantages are:

Time characteristics are defined by equations and graphs

Field selectable time characteristics

Very low burden extends the linear range of the CTs

Self-powered from the sensed current

Continuous automatic calibration

The BE1-50/51B-240 overcurrent relay may be tested without removing the relay from the case. Shorting
contacts are provided for all current inputs when the connection plugs or relay chassis is removed from
the relay case.

Specifications

BE1-50/51B-240 electrical and physical specifications are listed in the following paragraphs.

Time Overcurrent (51) Element

Pickup
Setting Range:

0.5 to 15.9 Aac

Setting Increment:

0.1 Aac

Accuracy:

Sum of

±2% and ±25 mAac

Dropout

Dropout occurs at 95% of pickup value.

Characteristic Curves

Available curve types follow IEEE Standard C37.112 (1996) and emulate standard GE IAC,
Westinghouse CO, and BS142 curves. The Characteristic Curves chapter illustrates the available curves
and lists the applicable constants.
Curve Types:

Short Inverse, Long Inverse, Definite Time, Moderately Inverse, Inverse,
Very Inverse, Extremely Inverse, BS142 Very Inverse, BS142 Extremely
Inverse, Fixed Time

Time Multiplier:

11 curves for each characteristic

Timing Accuracy:

±1 cycle, ±2%. This accuracy applies to the range of 1.3 to 40 times tap
and is for a given measured multiple of tap.

Fixed Timing
Setting Range:

0.1 to 9.9 s

Setting Increment:

0.1 s

Timing Accuracy:

±1 cycle, ±2% of the time to trip for time dial settings ≥0.1.

General Information

BE1-50/51B-240