Basler Electric BE1-50/51B-240 User Manual

Page 13

Advertising
background image

9252000790 Rev B

5

Target Indicators

A gravity-latched, manually-reset, current-operated target indicator is provided for the time-overcurrent
(51) trip output and the instantaneous overcurrent (50) trip output. The level of trip circuit current required
to operate each target is individually controlled by a circuit board jumper. See the Controls and Indicators
chapter for jumper locations and function assignments

Target Operate Current

Jumper Position—Pins 1 and 2: Must operate

≥ 2.25 A; must not operate < 900 mA.*

Jumper Position—Pins 2 and 3: Must operate

≥ 200 mA; must not operate < 80 mA.*

∗ See Output Contacts for the maximum acceptable levels of trip circuit currents.

Output Contacts

Output contacts are surge protected and rated as follows.

Resistive Ratings

120/240 Vac:

Make 30 amperes for 0.2 seconds, carry 7 amperes for 2 minutes, 3
amperes continuously, and break 5 amperes.

125/250 Vdc:

Make 30 amperes for 0.2 seconds, carry 7 amperes for 2 minutes, 3
amperes continuously, and break 0.3 ampere.

Inductive Ratings

120/240 Vac, 125/250 Vdc:

Make and carry 30 amperes for 0.2 seconds, carry 7 amperes for 2
minutes, 3 amperes continuously, and break 0.3 ampere. (L/R = 0.04).

Terminal Assignments
51 Element:

1, 10

50 Element:

2, 10

Type Tests

Isolation:

IEEE C37.90-2005

Transient Surge:

IEEE C37.90.1-2004

Radiated Interference:

IEEE C37.90.2-2004

Electrostatic Discharge:

IEEE C37.90.3-2006

Vibration:

IEC 255-21-1

Shock and Bump:

IEC 255-21-2

Environment

Operating Temperature:

–40 to 70

°C (–40 to 158°F)

Storage Temperature:

–50 to 70

°C (–58 to 158°F)

Physical

Weight:

4.3 lb (2 kg)





BE1-50/51B-240

General Information

Advertising