Functional description, Introduction, Function block descriptions – Basler Electric BE1-50/51B-240 User Manual

Page 19

Advertising
background image

9252000790 Rev B

11

Functional Description

Introduction

This chapter illustrates and describes the functional capabilities of the BE1-50/51B-240 relay.

Function Block Descriptions

BE1-50/51B-240 function blocks are illustrated in Figure 6 and described in the following paragraphs.

Figure 6. Function Block Diagram

Current Sensing Input

Single-phase ac current supplied by a system current transformer (CT) is applied to the BE1-50/51B-240
through terminals 8 and 9. Sensing current is applied to internal power and signal CTs.

Power CT and Power Supply

The output of the power CT is supplied to the power supply which provides rectified and filtered operating
power for all relay circuitry. A precision 5 Vdc output of the power supply serves as a reference for
automatic calibration.

Signal Conditioning

Current from the signal CT is rectified and applied to two independent sets of scaling resistors controlled
by the Time Overcurrent (51) and Instantaneous Overcurrent (50) pickup switches. The analog-to-digital
converter receives the analog voltage developed across the scaling resistors and converts it into a digital
signal that is supplied to the microprocessor.

Microprocessor

The microprocessor performs program operations based on the sensed current, switch settings, and the
internal software program.

BE1-50/51B-240

Functional Description

Advertising