Time overcurrent characteristics, Kbd c m ad t – Basler Electric BE1-50/51B-240 User Manual

Page 32

Advertising
background image

24

9252000790 Rev B

Time Overcurrent Characteristics

Nine inverse time functions and one fixed (definite) time function can be selected at the front panel. Curve
types are identified by a letter designator. Available curve types are short inverse (S), long inverse (L),
definite time (D), moderately inverse (M), inverse (I), very inverse (V), extremely inverse (E), BS142
inverse, (B), and BS142 extremely inverse (C).

Inverse Time Functions

Characteristic curves for the inverse and definite time functions are defined by the following equation:

K

BD

C

M

AD

T

N

T

+

+

=

Where: T

T

= time to trip in seconds

D = time dial setting

M = multiple of pickup setting

A, B, C, N, K =

constants for the particular curve

Characteristic Curve Groups

Either GE IAC or Westinghouse CO characteristic curve groups are selected through switch SW3-3.
(Refer to Figure 5 for the location of SW3.)

Characteristic Curve Constants

Table 4 and Table 5 list the time characteristic curve constants used by the relay. Constants have been
selected to conform to the characteristics of electromechanical relays over a range of pickup multiples
from 1.3 to 40. Values of the constants are provided for use in PC relay setting applications. Timing
accuracy is

±1 cycle ±2% of time to trip.

Table 4. Time Characteristic Curve Constants with Switch SW3-3 Open (Off)

Curve

Type

Similar To

Figure

Number

Constants

BE

A

B

C

N

K

R

S

CO-2

A-2

0.2663

0.03393

1.000

1.2969

0.028

0.500

L

CO-5

A-3

5.6143

2.18592

1.000

1.0000

0.028

15.750

D

CO-6

A-4

0.4794

0.21359

1.000

1.5625

0.028

0.875

M

CO-7

A-5

0.3022

0.12840

1.000

0.5000

0.028

1.750

I

CO-8

A-6

8.9341

0.17966

1.000

2.0938

0.028

9.000

V

CO-9

A-7

5.4678

0.10814

1.000

2.0469

0.028

5.500

E

CO-11

A-8

7.7624

0.02758

1.000

2.0938

0.028

7.750

B

BS142-B

A-9

1.4636

0.00000

1.000

1.0469

0.028

3.250

C

BS142-C

A-10

8.2506

0.00000

1.000

2.0469

0.028

8.000

F

None†

None

0.0000

1.00000

0.000

0.0000

0.000

1.000

∗ Curves B and C are defined in British Standard BS142 and IEC 255-4 (International

Electrotechnical Commission).

Fixed time from 0.1 to 9.9 seconds.

Characteristic Curves

BE1-50/51B-240

Advertising