Application coordination – Basler Electric BE1-50/51B-240 User Manual

Page 23

Advertising
background image

9252000790 Rev B

15

Figure 8. Typical DC Connections

Application Coordination

In a typical application coordination scheme, a BE1-50/51B-240 is used to provide distribution protection.
An electromechanical overcurrent relay with extremely inverse timing provides protection for the
transformer and bus. To improve coordination with the electromechanical relay, the BE1-50/51B-240 is
configured with the following settings:

Integrating reset enabled (SW3-4 ON)

Westinghouse CO type curves selected (SW3-3 OFF)

The feeder reclosing relay is set for two reclose attempts at 3 and 15 seconds after the initial trip. If a
permanent fault occurs (magnitude 10 times pickup), calculate the feeder breaker trip time for each of the
three operations. Refer to the Characteristic Curves chapter for the characteristic curve constants and
definition of the terms used in the following time characteristic curve equations.

From the time characteristic curve equation:

K

BD

C

M

AD

T

N

T

+

+

=

028

.

0

)

2

02758

.

0

(

1

10

2

7624

.

7

0938

.

2

+

×

+

×

=

= 0.209 seconds

BE1-50/51B-240