Installation, General, Factory settings – Basler Electric BE1-50/51B-240 User Manual

Page 21

Advertising
background image

9252000790 Rev B

13

Installation

General

When not shipped as part of a control or switchgear panel, the relays are shipped in sturdy cartons to
prevent damage during transit. Immediately upon receipt of a relay, check the model and part number
against the requisition and packing list to see that they agree. Visually inspect the relay for damage that
may have occurred during shipment. If there is evidence of damage, immediately file a claim with the
carrier and notify the Regional Sales Office, or contact the Sales Representative at Basler Electric,
Highland, Illinois.

Proper operation of the relay may be confirmed by performing the operational test procedures of the
Testing chapter. If the relay will not be installed immediately, store the relay in its original shipping carton
in a moisture- and dust-free environment.

Factory Settings

BE1-50/51B-240 jumpers and internal switch SW3 are configured at the factory as follows:

SW3-1: OFF (60-hertz operation)

SW3-2: OFF (0.0 additional fixed delay for the instantaneous element)

SW3-3: OFF (Westinghouse CO type characteristic curves)

SW3-4: ON (Integrating reset characteristics)

J1 pins 2 and 3: 50 minimum target operating current of 80 to 200 mA

J2 pins 2 and 3: 51 minimum target operating current of 80 to 200 mA

Installation

Note

If replacing a CO relay manufactured prior to 1966, please contact
Basler Electric to verify compatibility.

Select the desired relay settings before putting the relay into service. Changing pickup current settings
while the relay is in service may cause tripping. Perform the following procedures to install the
BE1-50/51B-240 relay.

1.

Select the desired relay settings on your new BE1-50/51B-240 relay.

2.

Remove the existing ABB/Westinghouse relay cradle.

3.

Insert the new relay cradle and close the knife-blade switches.

4.

Install the new Basler Electric replacement cover glass into existing cover and secure with the
captive thumbnut.

BE1-50/51B-240

Installation

Advertising