Instantaneous overcurrent (50) element, Current sensing input – Basler Electric BE1-50/51B-240 User Manual

Page 11

Advertising
background image

9252000790 Rev B

3

Reset
Integrating:

Simulates the disk reset of electromechanical relays and begins when
the current decreases below 95% of pickup. The Characteristic Curves
chapter illustrates the integrating reset characteristic curve and equation.

Instantaneous:

Reset occurs within 16 ms of when the current decreases below 95% of
the pickup level.

Instantaneous Overcurrent (50) Element

Pickup
Setting Range:

2 to 99 Aac

Setting increment:

1 Aac

Accuracy:

Sum of

±2% and ±25 mAac

Dropout

Dropout occurs at 95% of pickup value.

Time Delay
Switch selectable—no intentional delay (SW3-2 OFF) or a fixed delay of 100 ms (SW3-2 ON). The
Characteristic Curves chapter illustrates the characteristic curve for the 50 element.

Current Sensing Input

Continuous Rating:

14 Aac

1 Second Rating:

400 Aac

∗ Continuous rating is 14 Aac for temperatures up to 45°C. See Figure 1 for de-rating curve.

Figure 1. Current Sensing Input De-rating Curve

Burden

Figure 2 illustrates the current sensing input burden characteristic.

At 0.5 Aac:

2.8

Ω

At 5.0 Aac:

0.3

Ω

Continuous Current

Current Sensing Input

0

2

4

6

8

10

12

14

16

-40

-20

0

20

40

60

Ambient Temperature (C)

Cu

rre

n

t (

Aa

c

)

BE1-50/51B-240

General Information