Basler Electric BE1-50/51B-241 User Manual

Page 11

Advertising
background image

9252000792 Rev D

3


Reset
Integrating:

Simulates the disk reset of electromechanical relays and begins
when the current decreases below 95% of pickup. The
Characteristic Curves chapter illustrates the integrating reset
characteristic curve and equation.

Instantaneous:

Reset occurs within 16 ms of when the current decreases below
95% of the pickup level.

Instantaneous Overcurrent A (50-A) Element

Pickup
Setting Range:

2 to 99 Aac

Setting increment:

1 Aac

Accuracy:

Sum of

±2% and ±25 mAac

Dropout

Dropout occurs at 95% of pickup value.

Time Delay

Switch selectable with no intentional delay (SW3-2 OFF) or a fixed delay of 100 ms (SW3-2 ON). The
Characteristic Curves chapter illustrates the characteristic curve for the 50-A and 50-B elements.

Instantaneous Overcurrent B (50-B) Element

Pickup
Setting Range:

1 to 15.9 Aac

Setting increment:

0.1 Aac

Accuracy:

Sum of

±2% and ±25 mAac

Dropout

Dropout occurs at 95% of pickup value.

Time Delay

Fixed at no intentional delay. The Characteristic Curves chapter illustrates the characteristic curves for
the 50-A and 50-B elements.

Reset Characteristic

Resets within 16 ms of when sensed current decreases below the pickup level.

Current Sensing Input

Continuous Rating:

14 Aac

1 Second Rating:

400 Aac

∗ Continuous rating is 14 Aac for temperatures up to 45°C. See Figure 1 for de-rating curve.

BE1-50/51B-241