9252000792 Rev D

5

Frequency Response

A change of

±5 Hz from the nominal 50/60 Hz current causes <0.5% change in the current required for

pickup.

Transient Response

<10% overreach with system time constants up to 40 ms.

Harmonic Rejection

Rejection of odd and even harmonics is illustrated in Figure 3.

Figure 3. Harmonic Rejection

Target Indicators

A gravity-latched, manually-reset, current-operated target indicator is provided for the time-overcurrent
(51) trip output and the instantaneous overcurrent A (50-A) trip output. A target indicator is not provided
for the 50-B trip output. The level of trip circuit current required to operate each target is individually
controlled by a circuit board jumper. See the Controls and Indicators chapter for jumper locations and
function assignments

Target Operate Current
Jumper Position—Pins 1 and 2:

Must operate

≥ 2.25 A; must not operate < 900 mA.

*

Jumper Position—Pins 2 and 3:

Must operate

≥ 200 mA; must not operate < 80 mA.

*

∗ See Output Contacts for the maximum acceptable levels of trip circuit currents.

Output Contacts

Output contacts are surge protected and rated as follows.

Resistive Ratings
120/240 Vac:

Make 30 amperes for 0.2 seconds, carry 7 amperes for 2
minutes, 3 amperes continuously, and break 5 amperes.

BE1-50/51B-241