Basler Electric BE1-50/51B-241 User Manual

Page 27

Advertising
background image

9252000792 Rev D

19

k.

Set INST PICKUP (50-B) (accessed at the top side of the assembly) to F0 (15.0 Aac).

2.

Apply 4.0 Aac to terminals 8 and 9. After the unit trips, remove the applied current for 29

±0.25

seconds, then reapply the current (4.0 Aac). Note the elapsed time from the reapplication of current to
the second trip. The elapsed time should be 2.08

±0.4 seconds.

Instantaneous Overcurrent A (50-A) Pickup

1.

Connect and configure the relay for 50-A pickup testing:

a.

Connect the test setup shown in Figure 10.

b.

Set circuit board switch SW3 as follows:
SW3-1 = ON for 50 Hz operation or OFF for 60 Hz operation
SW3-2 = OFF (no additional time delay for the 50-A element)
SW3-3 = ON (Westinghouse CO/COM type characteristic curves)
SW3-4 = ON (integrating reset characteristic)

c.

Set TIME DIAL to 0.0.

d.

Set CURVE to S.

e.

Set TIME PICKUP to 15.0.

f.

Set INST PICKUP (50-A) to 02.

g.

Set INST PICKUP (50-B) (accessed at the top side of the assembly) to F0 (15.0 Aac).

2.

Apply and slowly increase current to terminals 8 and 9 until the 50-A output contacts close. The
applied current should be between 1.935 and 2.065 Aac.

3.

Decrease the applied current until the 50-A output contacts open.

4.

Set INST PICKUP (50-A) to 08.

5.

Slowly increase the current applied to terminals 8 and 9 until the 50-A output contacts close. The
applied current should be between 7.815 and 8.185 Aac.

6.

Reduce the applied current to zero.

Figure 10. 51 Pickup, Time Dial, Integrating Reset, and 50-A Pickup Test Setup

Instantaneous Overcurrent B (50-B) Pickup

1.

Connect and configure the relay for 50-B pickup testing:

a.

Connect the test setup shown in Figure 11.

BE1-50/51B-241

Testing

Advertising