Integrating time reset characteristic – Basler Electric BE1-50/51B-241 User Manual

Page 48

Advertising
background image

40

9252000792 Rev D

Timing Accuracy

Timing accuracy is the sum of

±1 cycle, ±2%. This accuracy applies to the range of 1.3 to 40 times tap

and is for a given measured multiple of tap. Measurement accuracy of the multiple of tap is the sum of
±2%, ±25 mA.

Fixed Time Characteristic

The fixed time characteristic corresponds to the time dial setting and provides delays of 0.0 to 9.9
seconds. The time setting is constant over a range of pickup multiples from 1.0 to 40. Accuracy is

±1

cycle,

±2% of the time to trip for time dial settings of 0.1 and greater.

Integrating Time Reset Characteristic

The relay can be user-configured for integrating or instantaneous type reset.

Integrating reset simulates the disk reset of electromechanical relays and begins when the current
decreases below 95% of pickup. BE1-50/51B-241 relays provide the integrating reset function even when
input current decreases to zero.

Integrating reset characteristics are defined by the following equation and are illustrated in Figure 28. See
Table 4 and Table 5 for the equation constants.

1

2

=

M

RD

T

R

Where:

T

R

= time to reset in seconds

R

= constant for the particular curve

D

= time dial setting

M = current in multiples of pickup setting during reset

Figure 28. Integrating Reset Characteristic Curve

Time characteristic curve equation:

Trip

to

Time

=

+

+

=

K

BD

C

M

AD

T

N

T

Where:

D

= time dial setting

M = multiple of pickup setting

Characteristic Curves

BE1-50/51B-241