Set circuit board switch SW3 as follows:
SW3-1 = ON for 50 Hz operation or OFF for 60 Hz operation
SW3-2 = OFF (no additional time delay for the 50-A element)
SW3-3 = ON (Westinghouse CO/COM type characteristic curves)
SW3-4 = ON (integrating reset characteristic)

c.

Set TIME DIAL to 0.0.

d.

Set CURVE to S.

e.

Set TIME PICKUP to 15.0.

f.

Set INST PICKUP (50-A) to 90.

g.

Set INST PICKUP (50-B) (accessed at the top side of the assembly) to 20 (2.0 Aac).

2.

Apply and slowly increase current to terminals 8 and 9 until the 50-B output contacts close. The
applied current should be between 1.935 and 2.065 Aac.

3.

Decrease the applied current until the 50-B output contacts open.

4.

Set INST PICKUP (50-B) to 80 (8.0 Aac).

5.

Slowly increase the current applied to terminals 8 and 9 until the 50-B output contacts close. The
applied current should be between 7.815 and 8.185 Aac.

6.

Reduce the applied current to zero.

Figure 11. 50-B Pickup Test Setup

Target Indicators

1.

Connect and configure the relay for target indicator testing:

a.

Connect the test setup shown in Figure 12.

b.

Set circuit board switch SW3 as follows:
SW3-1 = ON for 50 Hz operation or OFF for 60 Hz operation
SW3-2 = OFF (no additional time delay for the 50-A element)
SW3-3 = ON (Westinghouse CO/COM type characteristic curves)
SW3-4 = ON (integrating reset characteristic)

c.

Set TIME DIAL to 0.0.

d.

Set CURVE to S.

e.

Set TIME PICKUP to 1.0.

f.

Set INST PICKUP (50-A) to 90.