9252000994 Rev P

BE1-50/51B-214/-215/-223/-225 General Information

1-1

SECTION 1 • GENERAL INFORMATION

Introduction

BE1-50/51B-214/-215/-223/-225 protective relays are direct replacements for General Electric, IAC relays.

The BE1-50/51B-214/-215/-223 has a 5 ampere current sensing input. The BE1-50/51B-225 has a 1

ampere current sensing input. Compatible IAC model numbers are listed in Table 1-1.

Table 1-1. GE IAC Relays Suitable For Direct Replacement

IAC Model Number

Curve Type

12IAC51A∗∗∗A

Inverse

12IAC51B∗∗∗A

Inverse with Instantaneous

12IAC53A∗∗∗A

Very Inverse

12IAC53B∗∗∗A

Very Inverse with Instantaneous

12IAC55A∗∗∗A

Short Time

12IAC55B∗∗∗A

Short Time with Instantaneous

12IAC66A∗∗A

Long Time

12IAC66B∗∗A

Long Time with Instantaneous

12IAC77A∗∗∗A

Extremely Inverse

12IAC77B∗∗∗A

Extremely Inverse with Instantaneous

Any digit covering all pickup ranges and 50 Hz or 60 Hz models.

To replace an existing IAC relay, perform the following steps.

1. Select the desired relay settings on your new BE1-50/51B-214/-215/-223/-225 relay.

2. Remove the existing IAC relay.

3. Attach the cover adapter to the existing case.

4. Insert the new relay.

5. Install the new Basler Electric connection plug.

6. Install the new Basler Electric cover.

Basler Electric BE1-50/51B-214/-215/-223/-225 protective relays are self-powered, microprocessor-

based, non-directional phase or ground relays that monitor the magnitude of a single-phase ac current to

provide accurate instantaneous and time overcurrent protection for 50 Hz or 60 Hz power systems. Each

model covers 10 popular time characteristics and a wide range of pickup settings.

Features

A wide range of pickup settings and front panel selectable time characteristics permit applications

involving coordination with fuses, reclosers, cold load pickup, motor starting, and fixed time requirements.

Also, an integrating reset function is available to simulate the disk reset of electromechanical relays.
BE1-50/51B-214/-215/-223/-225 overcurrent relays have the following standard features.

Independent time and instantaneous elements

A secure method to manually trip the breaker at the relay front panel

Direct reading front panel controls

Minimum pickup setting for safety during installation

Time characteristics extend to a pickup multiple of 40

Rugged draw-out construction with steel case

Gravity latching targets retain indication without power

Built-in accuracy eliminates internal adjustments

Minimum transient overreach

Field selectable characteristic curve selection similar to either GE IAC or ABB type curves

Field selectable instantaneous or integrating reset

Field selectable 50 or 60 Hz operation

Field selectable 0.0 or 0.1 second, fixed, instantaneous delay