BE1-50/51B-214/-215/-223/-225 General Information

9252000994 Rev P

Figure 1-4. Harmonic Rejection

Target Indicators

Gravity latched, manually reset targets indicate that current of 0.2 amperes or greater was present in the

trip circuit. Target coil resistance is less than 0.1 ohms and operate time is less than one millisecond. See

Output Contacts for maximum current rating.

Output Contacts

Output contacts are surge protected and rated as follows.

Resistive Ratings

120/240 Vac ............................... Make 30 amperes for 0.2 seconds, carry 7 amperes for 2 minutes, 3

amperes continuously, and break 5 amperes.

125/250 Vdc ............................... Make 30 amperes for 0.2 seconds, carry 7 amperes for 2 minutes, 3

amperes continuously, and break 0.3 ampere.

Inductive Ratings

120/240 Vac, 125/250 Vdc ........ Make and carry 30 amperes for 0.2 seconds, carry 7 amperes for 2

minutes, 3 amperes continuously, and break 0.3 ampere. (L/R = 0.04).

Type Tests

Isolation ..................................... IEEE C37.90-2005

Transient Surge ......................... IEEE C37.90.1-2004

Radiated Interference ................ IEEE C37.90.2-2004

Electrostatic Discharge .............. IEEE C37.90.3-2006

Vibration ..................................... IEC 255-21-1

Shock and Bump ....................... IEC 255-21-2