Periodic test, Periodic test -9 – Basler Electric BE1-50/51B-121 User Manual

Page 53

Advertising
background image

9252000994 Rev P

BE1-50/51B-214/-215/-223/-225 Testing

5-9

sense all types of faults on a grounded wye system. Refer to Figures 5-1 through 5-4 for recommended

test setups.

Periodic Test

Periodic testing should consist of the following procedures.
Step 1. Verify that the instantaneous pickup is within ±2% of the value set on the dials. Pickup occurs

when the INST output contacts close.

Step 2. Verify that the time pickup is within ±2% of the value set on the dials. Pickup occurs when the

LED turns GREEN then RED.

Step 3. Verify that the time to trip for the curve and time dial settings at a multiple of six is the same as

the time given on the characteristic curve. Refer to Section 1 for the characteristics curves.

Step 4. Verify that the time to trip for the instantaneous element at a pickup multiple of 2 is not greater

than the time given on the instantaneous characteristic curve. Refer to Section 1 for the

instantaneous characteristic curve.

Step 5. Verify that the targets operate with one ac ampere of trip current in the trip circuits and that they

can be reset using the RESET BUTTON.