General, Factory settings, Installation – Basler Electric BE1-50/51B-121 User Manual

Page 37: Application coordination, Section 4 • installation -1, General -1, Factory settings -1, Installation -1, Application coordination -1

Advertising
background image

9252000994 Rev P

BE1-50/51B-214/-215/-223/-225 Installation

4-1

SECTION 4 • INSTALLATION

General

When not shipped as part of a control or switchgear panel, the relays are shipped in sturdy cartons to

prevent damage during transit. Immediately upon receipt of a relay, check the model and part number

against the requisition and packing list to see that they agree. Visually inspect the relay for damage that

may have occurred during shipment. If there is evidence of damage, immediately file a claim with the

carrier and notify the Regional Sales Office, or contact the Sales Representative at Basler Electric,

Highland, Illinois.
Proper operation of the relay may be confirmed by performing the operational test procedure of Section 5.

If the relay won't be installed immediately, store the relay in its original shipping carton in a moisture and

dust-free environment.

Factory Settings

Factory settings for the internal switches of SW3 are as follows:

SW3-1 — OFF (60 hertz operation).

SW3-2 — OFF (0.0 additional fixed delay for the instantaneous element).

SW3-3 — ON (GE IAC type characteristic curves).

SW3-4 — ON (Integrating reset characteristics).

Installation

Select the desired relay settings before putting the relay into service. Changing pickup current settings

while the relay is in service may cause tripping. Perform the following procedures to install the BE1-

50/51B-214/-215/-223/-225 relay.

Select the desired relay settings on your new BE1-50/51B-214/-215/-223/-225 relay.

Remove the existing IAC relay.

Use the four screws provided and attach the cover adapter to the existing case.

Insert the new relay and close the cradle latches locking the relay into the case.

Install the new Basler Electric connection plug.

To install the cover, position the interlocking bracket at the top of the new Basler Electric cover

into the mating receptacle at the top of the cover adapter plate. Secure the captive fastener at the

bottom of the cover.

Application Coordination

In a typical application coordination scheme, a BE1-50/51B-214/-215/-223/-225 is being used to provide

primary protection for a radial distribution feeder. An electromechanical overcurrent relay with extremely

inverse timing provides protection for the transformer and bus. To improve coordination with the

electromechanical relay, the BE1 relay with integrating reset characteristic has the time characteristic

curve E (extremely inverse) selected (SW3-3 set to OFF) and the TIME DIAL set to 2.0. The feeder

reclosing relay is set for two reclose attempts at 3 and 15 seconds after the initial trip. If a permanent fault

occurs (magnitude ten times pickup), calculate the feeder breaker trip time for each of the three

operations. Refer to Section 1 for characteristic curve constants.
From the time characteristic curve equation.

K

BD

C

M

AD

T

N

Trip

+

+

=

(

)

028

0

2

02758

.

0

1

10

2

7624

7

0938

2

.

.

.

+

×

+

×

=

028

0

05516

.

0

1

10806

124

5248

15

.

.

.

+

+

=

seconds

0.209

=