BE1-50/51B-214/-215/-223/-225 General Information

9252000994 Rev P

Internal switches provide for selecting system operating frequencies of 50 or 60 Hz, instantaneous

element delays of 0.0 or 0.1 second, characteristic curve group selection for either GE IAC or ABB type

curves, and instantaneous or integrating reset characteristics. Switch location and description is provided

in Section 2.

Advantages

BE1-50/51B-214/-215/-223/-225 overcurrent relays have many advantages over other overcurrent relays.

The primary advantages are:

Time characteristics are defined by equations and graphs

Field selectable time characteristics

Very low burden extends the linear range of the CTs

Self powered from the sensed current

Continuous automatic calibration

BE1-50/51B-214/-215/-223/-225 overcurrent relays may be tested without removing the relay from the

case. Shorting contacts are provided for all current inputs when the connection plugs or relay chassis is

removed from the relay case.

Specifications

BE1-50/51B-214/-215/-223/-225 overcurrent relays have the following features and capabilities.

Current Sensing Input
BE1-50/51B-214/-215/-223

Continuous Current.................... 14 Aac

One Second Rating ................... 400 Aac

BE1-50/51B-225

Continuous Current.................... 2.8 Aac

One Second Rating ................... 80 Aac

Time Overcurrent (51) Element

Setting the TIME PICKUP control at the minimum pickup setting places the relay in the most sensitive

state and may be used as a safety setting.

BE1-50/51B-214/-215/-223 Pickup

Setting Range ............................ 0.5 to 15.9 Aac

Setting Increment ....................... 0.1 Aac

Accuracy .................................... ±2%, ±25 milliamperes at or above 0.5 ampere setting

BE1-50/51B-225 Pickup

Setting Range ............................ 0.1 to 3.18 Aac

Setting Increment ....................... 0.02 Aac

Accuracy .................................... ±2%, ±5 milliamperes at or above 0.1 ampere setting

Dropout

Dropout occurs at 95% of pickup value.

Timing Range

0.0 to 9.9 seconds in 0.1 second steps.

Timing Accuracy

The timing accuracy is the sum of ±1 cycle, ±2%. This accuracy applies to the range of 1.3 to 40 times tap

and is for a given measured multiple of tap. The measurement of the multiple of tap has an accuracy that

is the sum of ±2%, ±25 milliamperes for the BE1-50/51B-214/-215/-223 and ±2%, ±5 milliamperes for the

BE1-50/51B-225.