BE1-50/51B-214/-215/-223/-225 General Information

1-5

Figure 1-1. Integrating Reset Characteristic Curve

Instantaneous Overcurrent (50) Element

Setting the INST PICKUP control to the minimum pickup setting places the relay in the most sensitive

state and may be used as a safety setting.

BE1-50/51B-214/-215/-223 Pickup

Setting Range ............................ 1 to 99 Aac

Setting Increment....................... 1 Aac

Accuracy .................................... ±2%, ±25 milliamperes at or above 1.0 ampere setting

BE1-50/51B-225 Pickup

Setting Range ............................ 0.2 to 19.8 Aac

Setting Increment....................... 0.2 Aac

Accuracy .................................... ±2%, ±2 milliamperes at or above 0.2 ampere setting

Dropout

Dropout occurs at 95% of pickup value.

Curve Characteristics

Instantaneous characteristic curves are similar to standard electromechanical instantaneous units.

However, the time to trip for applications where the initial current through the relay is less than 0.4

ampere (5 ampere relay) or 0.08 ampere (1 ampere relay) may be slightly longer. This may occur on a

very lightly loaded circuit or when the relay is providing ground protection and is connected to measure

neutral current. Figure 1-2 shows the instantaneous characteristic curves for maximum time to trip.
An additional fixed delay of 0.1 second may be added with internal switch SW3-2. This delay applies to

both phase and ground applications. Closing switch SW3-2 provides an additional delay of 0.1 second.

Section 2 illustrates the location of SW3.
The instantaneous element in BE1-50/51B-214/-215/-223/-225 relays may be set lower than the

instantaneous element in IAC relays and still have the same reach. This is because the BE1-50/51B-214/-

215/-223/-225 instantaneous element effectively eliminates the fault current transient overreach

components. When calculating BE1-50/51B-214/-215/-223/-225 relay instantaneous element settings,

calculate the symmetrical value without any adder for transient overreach.

1.0

10.0

100.0

0.000

0.200

0.400

0.600

0.800

1.000

1.200

Multiple of Pickup

xR

D

(S

ec

on

ds

)

P0

04

6-

11

Vertical axis xRD (Seconds) is applicable for all curves and is derived from

multiplying the constant R for the curve selected times D (the Time Dial setting).