Integrating reset, Table – Basler Electric BE1-50/51B-121 User Manual

Page 16

Advertising
background image

1-4

BE1-50/51B-214/-215/-223/-225 General Information

9252000994 Rev P

Table 1-3. Time Characteristic Curve Constants with SW3-3 Closed (On)

Curve Type *

Figure

Number

Constants

BE1

Similar To

A

B

C

N

K

R

S

GE IAC 55

A-10

0.0286

0.0208

1.000

0.9844

0.028

0.0940

L

GE IAC 66

A-11

2.3955

0.00002

1.000

0.3125

0.028

7.8001

D

ABB CO-6

A-3

0.4797

0.21359

1.000

1.5625

0.028

0.8750

M

ABB CO-7

A-4

0.3022

0.12840

1.000

0.5000

0.028

1.7500

I

GE IAC 51

A-12

0.2747

0.1042

1.000

0.4375

0.028

0.8868

V

GE IAC 53

A-13

4.4309

0.0991

1.000

1.9531

0.028

5.8231

E

GE IAC 77

A-14

4.9883

0.0129

1.000

2.0469

0.028

4.7742

B

BS142-B ‡

A-8

1.4636

0.00000

1.000

1.0469

0.028

3.2500

C

BS142-C ‡

A-9

8.2506

0.00000

1.000

2.0469

0.028

8.0000

F

None §

N/A

0.0000

1.00000

0.000

0.0000

0.000

1.0000


Notes for Table
*

BE1 Curve Types:

S: Short InverseV: Very Inverse

s 1-2 and 1-3

L: Long InverseE: Extremely Inverse

D: Definite TimeB: BS142 Very Inverse

M: Moderately Inverse

C: BS142 Extremely Inverse

I: Inverse F: Fixed Time Delay

† Figure numbers refer to the characteristic curves located in Appendix A, Time Characteristic Curves.
‡ Curves B and C are defined in British Standard BS142 and IEC Standard IEC 255-4.
§ Fixed time delay, adjustable from 0.1 to 9.9 seconds.

Integrating Reset

Reset begins when the current drops below 95% of pickup. Integrating reset simulates the disk reset of

electromechanical relays. BE1-50/51B-214/-215/-223/-225 relays provide the integrating reset function

even when input current falls to zero.
Integrating reset characteristics are defined by the following equation and shown in Figure 1-1. Equation

constants are provided in Tables 1-2 or 1-3.

Integrating Reset Equation:

1

M

RD

T

2

R

=

Where:

T

R

= Time to reset in seconds

R = Constant for the particular curve

D = TIME DIAL setting

M = Current in multiples of PICKUP setting during reset

Advertising