Specifications, Time overcurrent (51) element, Be1-50/51b-230/-239 pickup – Basler Electric BE1-50/51B-230 User Manual

Page 12: Be1-50/51b-234 pickup, Dropout, Characteristic curves, Fixed timing, Reset, Instantaneous overcurrent a (50-a) element, Time delay

Advertising
background image

1-2

BE1-50/51B-230/-234/-239 General Information

9252000894 Rev H

Specifications

BE1-50/51B-230, BE1-50/51B-234, and BE1-50/51B-239 electrical and physical specifications are listed

in the following paragraphs.

Time Overcurrent (51) Element

Setting Range ............................ 0.5 to 15.9 Aac

BE1-50/51B-230/-239 Pickup

Setting Increment ....................... 0.1 Aac

Accuracy .................................... Sum of ±2% and ±25 mAac

Setting Range ............................ 0.1 to 3.18 Aac

BE1-50/51B-234 Pickup

Setting Increment ....................... 0.02 Aac

Accuracy .................................... Sum of ±2% and ±5 mAac

Dropout occurs at 95% of pickup value.

Dropout

Available curve types follow IEEE Standard C37.112 (1996) and emulate standard GE IAC, ABB CO, and

BS142 curves. Appendix A, Characteristic Curves illustrates the available curves and lists the applicable

constants.

Characteristic Curves

Curve Types .............................. Short Inverse, Long Inverse, Definite Time, Moderately Inverse, Inverse,

Very Inverse, Extremely Inverse, BS142 Very Inverse, BS142 Extremely

Inverse, Fixed Time

Time Multiplier ........................... 11 curves for each characteristic

Timing Accuracy ........................ ±1 cycle, ±2%. This accuracy applies to the range of 1.3 to 40 times tap

and is for a given measured multiple of tap.

Setting Range ............................ 0.1 to 9.9 s

Fixed Timing

Setting Increment ....................... 0.1 s

Timing Accuracy ........................ ±1 cycle, ±2% of the time to trip for time dial settings ≥0.1.

Integrating .................................. Simulates the disk reset of electromechanical relays and begins when

the current decreases below 95% of pickup. Appendix A, Characteristic

Curves illustrates the integrating reset characteristic curve and equation.

Reset

Instantaneous ............................ Reset occurs within 16 ms of when the current decreases below 95% of

the pickup level.

Instantaneous Overcurrent A (50-A) Element

Setting Range ............................ 2 to 99 Aac

BE1-50/51B-230/-239 Pickup

Setting increment ....................... 1 Aac

Accuracy .................................... Sum of ±2% and ±25 mAac

Setting Range ............................ 0.4 to 19.8 Aac

BE1-50/51B-234 Pickup

Setting increment ....................... 0.2 Aac

Accuracy .................................... Sum of ±2% and ±5 mAac

Dropout occurs at 95% of pickup value.

Dropout

Switch selectable—no intentional delay (SW3-2 open/off) or a fixed delay of 100 ms (SW3-2 closed/on).

Appendix A, Characteristic Curves illustrates the characteristic curve for the 50-A and 50-B elements.

Time Delay

Advertising