BE1-50/51B-230/-234/-239 Functional Description

9252000894 Rev H

RC time constant. This provides information from the integrating reset function even when power has

been entirely removed.
The microprocessor defines the relay operating parameters based on inputs received from the Time

Overcurrent Time Dial Selector, Curve Selector, and four-position slide switch. The microprocessor

determines the level of sensed current by a digital signal supplied by the analog-to-digital converter.

Sensed current that exceeds the setting of the Time Overcurrent Pickup Selector switches causes the

Active/Pickup LED color to change from green to red and the 51 Trip output contacts to close in

accordance with the time characteristic equation. Sensed current exceeding the Instantaneous

Overcurrent A Pickup selector switch setting causes the 50-A Trip output contacts to close. Likewise,

sensed current exceeding the Instantaneous Overcurrent B Pickup selector switch setting causes the 50-

B Trip output contacts to close.

Outputs

Each protective element (time overcurrent (51), instantaneous overcurrent A (50-A), and instantaneous

overcurrent B (50-B)) is equipped with a set of normally-open contacts rated for tripping duty. A system

circuit breaker controlled by the 51 or 50-A output contacts can be manually tripped by connecting a

jumper across the Time Overcurrent Manual Trip jacks or the Instantaneous Overcurrent Manual Trip

jacks. (Manual trip jacks are not provided for the system circuit breaker controlled by the 50-B output

contacts.) Current flow in a trip circuit is indicated by operation of the corresponding target. The targets

will not operate without adequate relay operating power.

WARNING!

Trip circuit voltage is present at the front panel trip jacks. When shorting the

trip jacks, use insulated jumpers to avoid contact with these voltages.

Target Indicators

Gravity-latched, manually-reset, current-operated target indicators are provided for the time overcurrent

(51) trip output and the instantaneous overcurrent A (50-A) trip output. A target indicator is not provided

for the 50-B trip output. The level of trip circuit current required to operate each target is individually

controlled by a circuit board jumper. The minimum operating current range can be set for 80 to 200

milliamperes or 0.9 to 2.25 amperes. See Section 2, Controls and Indicators for jumper locations and

function assignments.