BE1-50/51B-230/-234/-239 General Information

9252000894 Rev H

Continuous Rating ..................... 2.8 Aac∗

BE1-50/51B-234

1 Second Rating ........................ 80 Aac

Continuous rating is 2.8 Aac for temperatures up to 45°C. See Figure 1-2 for derating curve.

Figure 1-2. Current Sensing Input Derating Curve (BE1-50/51B-234)

Figure 1-3

BE1-50/51B-230/-239 Burden

illustrates the current sensing input burden characteristic.

At 0.5 Aac .................................. 2.8 Ω

At 5.0 Aac .................................. 0.3 Ω

Figure 1-3. Current Sensing Input Burden (BE1-50/51B-230/-239)