BE1-50/51B-230/-234/-239 Installation

4-7

Figure 4-6. Typical DC Connections

Application Coordination

In a typical application coordination scheme, a BE1-50/51B-230, BE1-50/51B-234, or BE1-50/51B-239 is

used to provide primary protection for a radial distribution feeder. An electromechanical overcurrent relay

with extremely inverse timing provides protection for the transformer and bus. To improve coordination

with the electromechanical relay, the BE1-50/51B-230, BE1-50/51B-234, or BE1-50/51B-239 is

configured with the following settings:

Integrating reset enabled (SW3-4 ON)

Time characteristic curve E (extremely inverse) selected

ABB type curves selected (SW3-3 OFF)

Time dial set at 2.0

The feeder reclosing relay is set for two reclose attempts at 3 and 15 seconds after the initial trip. If a

permanent fault occurs (magnitude 10 times pickup), calculate the feeder breaker trip time for each of the

three operations. Refer to Appendix A for the characteristic curve constants and definition of the terms

used in the following time characteristic curve equations.
From the time characteristic curve equation:

K

BD

C

M

AD

T

N

T

+

+

=

028

.

0

)

2

02758

.

0

(

1

10

2

7624

.

7

0938

.

2

+

×

+

×

=

=

0.209 seconds