Auxiliary outputs, Push-to-energize pushbuttons, Power supply status output (option 3-6) – Basler Electric BE1-51/27R User Manual

Page 22: Target indicators

Advertising
background image

16

9137200999 Rev F

closed (output type G) contacts may be specified. (The contact configurations of all output relays for a
given model will be the same.)

Auxiliary Outputs

In addition to the output relays, an auxiliary relay, having the same or a different contact configuration,
may be specified. Both the output and the auxiliary relays will remain energized for the duration of the
overcurrent condition.

Push-to-Energize Pushbuttons

If either option 2-C or 2-E is present, each individual output relay can be directly energized for test
purposes by the actuation of a front panel PUSH-TO-ENERGIZE OUTPUT pushbutton. The pushbutton is
actuated by the insertion of a thin, non-conducting rod through an access hole in the front panel.

Power Supply Status Output (Option 3-6)

Power supply status output relays have a set of normally closed contacts that are energized open during
power-up. If either or both power supply output legs (+12 Vdc or

−12 Vdc) fails, the power supply status

output relay is de-energized and the output contacts close. Shorting bars across the output contacts are
held open by the installed connection plug. When the relay is removed from service by removing the
connection plug, the shorting bars are closed.

Target Indicators

Target indicators are optional components selected when a relay is ordered. The electronically latched
and reset targets consist of red LED indicators located on the relay front panel. A latched target is reset
by operating the target reset switch on the front panel. If relay operating power is lost, any illuminated
(latched) targets are extinguished. When relay operating power is restored, the previously latched targets
are restored to their latched state.

A relay can be equipped with either internally operated targets or current operated targets.

Internally Operated Targets

The relay trip outputs are directly applied to drive the appropriate target indicator. Each indicator is
illuminated regardless of the current level in the trip circuit.

Current Operated Targets

A current operated target is triggered by closure of the corresponding output contact and the presence of
at least 200 milliamperes of current flowing in the trip circuit.

Note that the front panel function targets (TIMED, INST 1, etc.) may be either internally or current
operated. Phase and neutral indicators are current operated only if the instantaneous options are not
included and if current operated targets are specified.

Note

Prior to August 2007, BE1-51/27R target indicators consisted of
magnetically latched, disc indicators. These mechanically latched
target indicators have been replaced by the electronically latched LED
targets in use today.

Functional Description

BE1-51/27R