Neutral element backup settings – Basler Electric BE1-51/27R User Manual

Page 67

Advertising
background image

9137200999 Rev F

61

Figure 38. Relay 51/27 Coordination with Relay 67 for Fault 3 Example

Neutral Element Backup Settings

(1) The 51N element has no relays to coordinate with because the generators are ungrounded. An

instantaneous element, if used, must be set above the maximum false residual current that can be
developed due to dissimilar current transformer saturation during an external three-phase fault.
Similarly, the time setting of the time overcurrent element must ride through this transient resulting
from current transformer saturation.

(2) Ground current contribution from each transformer is 485 amperes. Normal total current level is:

A

970

485

2

=

×

(3) Set the time element for 0.8-ampere pickup.

(4) Set the time element (51N) at 0.2 s for 970 amperes primary (see B3 curve):

DIAL

TIME

08

and

multiples

20

0.8

60

970

=

×

(5) Set the instantaneous (50N) pickup at 5 amperes:

7

.

6

0.8

5 =

The maximum ground fault current is:

pickup

Relay

the

times

2

.

3

300

970 =

BE1-51/27R

Tests and Adjustments