Basler Electric BE1-51/27R User Manual

Page 62

Advertising
background image

56

9137200999 Rev F

Figure 35. Relay Signals and Current Pickup Example for 3-Phase Fault (X

E

=0.65 X”

D

)

Figure 36 shows an example similar to Figure 35, but the higher external reactance (X

E

= 2X"

D

) to the fault

develops a higher restraint voltage. In Figure 36, the shaded area of the graph where pickup exceeds 25
percent of nominal is much larger than the shaded area in Figure 35. (This is the area where the relay
operates slower.) If we assume a fixed 25 percent of nominal pickup current, a significant margin in the
time coordination with external protection is added, although the log scale tends to exaggerate this effect.

Figure 36. Relay Signals and Current Pickup Example for 3-Phase Fault (X

E

=2 X”

D

)

Tests and Adjustments

BE1-51/27R

Advertising