Downstream current in Error! Reference source not found. is the current in the downstream relay with
which the BE1-51/27R elements must coordinate. The currents are the changes resulting from the fault
assuming a driving point voltage of 11 kV. Actual currents will be the sum of the table values plus the pre-
fault load currents. Transient level currents are based on use of the generator transient reactance.
Steady-state level currents are based on use of generator steady-state reactance and assuming no
generator regulator boost. Note that the table values apply for 3-phase faults. Transient level currents in
generators for a phase-to-phase fault will be about equal to the 3-phase current values. Steady-state level
currents in the generators will be higher for a phase-to-phase fault.

Table 7. Three-Phase Fault Currents

Level

Out of Service

Fault Loc.

Fault Current - A @ 11 kV

Downstream

Generator

Transient

T2

1

7256

776

Steady State

T2

1

5961

129

Transient

2

7256

776

Transient

T2

2

1552

776

Steady State

T2

2

258

129

Transient

3

713

713

Steady State

3

127

127

Coordination with Feeder 51 Relay for Fault 1

(1)

Multiples of pickup in 51 relay at transient level:

(

)

7.6

960

7256

6

800/5

7256

=

=

Tests and Adjustments

BE1-51/27R