Setting example – Basler Electric BE1-51/27R User Manual

Page 63

Advertising
background image

9137200999 Rev F

57

Setting Example

Error! Reference source not found. illustrates generator relay elements that are to be set in this
example. Plant 11 kV feeders are supplied by a 115 kV system that is supplemented by two local 3,700
kVA generators. Line 1 is illustrated completely; line 2 is the same as line 1 and only shows major
components. Settings are provided for the BE1-51/27R Time Overcurrent Relay with voltage restraint,
BE1-51 Time Overcurrent Relay, and BE1-67 Phase Directional Overcurrent Relay.

Generator Backup (Breaker A)

BE1-51/27R (51/27), relay style number: U3E B6S B2C0F

Three-phase-and-neutral overcurrent

1.5 to 12 A phase (instantaneous trip is out of service)

0.5 to 4 A neutral (instantaneous is in service)

Very inverse timing (B6)

300/5 CTs

Feeder (Breaker F)

BE1-51 (51)

0.5 to 12 A

Very inverse timing (B6)

800/5 CTs

No instantaneous

Pickup set to 6 A

Time Dial set to 08

Phase Directional (Breaker L)

BE1-67 (67)

0.5 to 12 A

Definite timing (B3)

3,000/5 CTs

Pickup set to 0.5 A

Time Dial set to 02

Generator Reactance (Per Unit)

Sub transient ........... 0.18

Transient ................. 0.25

Steady State ........... 1.5

BE1-51/27R

Tests and Adjustments