Ct polarity, Ct polarity -18, Figure 12-19. standard ct polarity -18 – Basler Electric BE1-CDS240 Installation User Manual

Page 20: Figure 12-20. current transformer action -18, Figure 12-21. example of reversed ct polarity -18

Advertising
background image

CT Polarity

CT polarity is critical to the proper operation of the BE1-CDS240. The sidebar below provides

fundamental information on CT polarity and protective relays.

Sidebar: Current Circuit Polarity

By ANSI convention, Current Transformer Polarity will face away from the protected winding of a

transformer, motor, generator, or reactor and away from the contacts in a circuit breaker. Therefore,

primary current flow towards the winding or contacts (direction of protected zone) will result in a

secondary current out X1, in phase with the primary. (See Figures 12-19 and 12-20.)

Figure 12-19. Standard CT Polarity

Figure 12-20. Current Transformer Action

On occasion, however, protection engineers will encounter situations where CT polarity is reversed for

a specific application. That is, non-polarity of the CT secondary will be in phase with the primary

current flow (Figure 12-21). For example, a transformer differential CT from a breaker with a different

polarity convention, such as low voltage switchgear or a bus differential CT taken from the low side of a

transformer.

Figure 12-21. Example of Reversed CT Polarity

Orientation of CT polarity relative to primary current flow establishes the secondary CT terminal that

should be connected to polarity of the protective relay.


12-18

BE1-CDS240 Installation

9365200990 Rev M

Advertising